Fire Alarm Systems
Fire Alarm Systems are required to be maintained in operable condition
at all times. As well, fire alarm systems shall be inspected in
conformance with ULC-S536 (per
the National Fire Code). This
sub-referenced code requires monthly and yearly testing to ensure
complete operability and help prevent false activations. Records
must be kept by the building owner/manager for examination by the
insuring agent and/or the authority having jurisdiction. Only technicians
who have completed the Canadian Fire Alarm
Association Technician Education Program, or an equivalent
course, or who is employed by a ULC
listed fire alarm service agency may perform maintenance and inspections.
Pyrene is the only ULC
listed fire alarm service agency in Manitoba and employs many technicians
who have completed the CFAA
Education Program.
|
 |
(Sample
Fire Alarm Inspection Report -
103K
) |
Sprinkler Systems
Automatic Sprinkler Systems (wet and dry) are required to be maintained
in operable condition at all times. Maintenance and inspection is
required monthly, quarterly and yearly as mandated by the National
Fire Code, section 6.5. These inspections ensure the
systems are operable and ready for use should the need arise. Records
must be kept by the building owner or manager for examination by
the insuring agent and/or the authority having jurisdiction.
|
 |
| (Sample
Sprinkler Systems Inspection Report -
126K
) |
Standpipe/Fire Pumps
Standpipe and fire pump systems are required to be maintained and
inspected monthly, quarterly and annually in accordance with NFPA
25. Flow tests of wet standpipe systems shall be performed every
5 years. Dry standpipes are required to be hydrostatically tested
every 5 years. Records must be kept by the building owner or manager
for examination by the insuring agent and/or the authority having
jurisdiction.
|
 |
(Sample
Standpipe Test Report (Wet System) -
85K
)
(Sample
Standpipe Test Report (Dry System) -
80K
)
(Sample
Fire Pump Test Report -
74K
) |
Fire
Hoses
As an extension of a standpipe system, a fire hose can mean the
difference between the success and failure of the delivery of water
to a fire. Proper maintenance, by the terms of NFPA
1961, requires an unfurling, visual inspection and re-racking annually.
Nozzles and all accessories must be inspected every year to ensure
there are no visible signs of deterioration in the quality of the
water-delivery system. A hydrostatic
test must be performed 5 years after the hose's initial date
of manufacture, and every 3 years there after.
|
 |
Emergency & Exit Lighting
Systems
Emergency lighting systems require test and inspections to be performed
monthly and annually. The National Fire
Code mandates systems should be checked to ensure they
operate in conformance with the manufacturers specifications.
Although reports are not required by code, a record can assist with
trouble-shooting and is veritable proof of inspections performed.
|
 |
| (Sample
Emergency Lighting Inspection Report -
69K
) |
Clean Agent Systems
Clean Agent Systems such as Halon, FM-200 and Inergen require inspection
semi-annually in accordance with the National
Fire Code and various sub-referenced NFPA
codes. Enclosure inspections and integrity testing, as warranted,
are essential to the continued efficiency of a total-flooding system.
|
 |
| (Sample
Extinguishing Systems Inspection Report -
85K
) |
CO2
Systems
NFPA 12 requires Carbon Dioxide
Fire Suppression Systems to be inspected semi-annually. Reliable
operation is essential for un-interrupted fire protection in industrial
facilities protected by systems such as these. Inspection and testing
of enclosure integrity is highly recommended to ensure proper operation
of any CO2 system.
|
 |
| (Sample
Extinguishing Systems Inspection Report -
85K
) |
Smoke Alarms
As the earliest warning in most fire situations, it is imperative
that smoke alarms are continuously operational. Whether operated
by 9V battery, 110VAC or a 10-year lithium cell, smoke alarms should
be tested yearly. For the safety of residents, and the liability
protection of owners/mangers, records should be kept on file as
proof of said tests.
Building owners/mangers operating buildings within the City of
Winnipeg should be aware of the special requirements of the Winnipeg
Fire Prevention By-law 1322/76 pertaining to Smoke Alarms for Residential
Rental Units when contracting for installation, repairs and maintenance
of smoke alarms.
|
 |
Portable Fire Extinguishers
Fire extinguishers are the essential weapon for first-strike combat
of any type of fire. As such,
they must always be pressurized and full. A partially charged, or
neglected extinguisher may not be reliable in a fire situation. All
occupancies covered by the National Fire Code require monthly and
annual inspections of portable extinguishers. Any dry chemical extinguisher,
whether for private or commercial use, should be disassembled, inspected
internally and re-built every 6 years and hydrostatically tested every
12 years. Extinguishers containing other agents are subject to other
periodic maintenance. The Manitoba Fire Code
dictates that only certified agencies may perform inspections and
service in Manitoba. Pyrene Fire Security Manitoba
is a ULC listed fire extinguisher
service agency and strictly adheres to the practices laid out in ULC-S532. |
 |
Kitchen Fire Suppression Systems
Wet and dry kitchen suppression systems shall be inspected semi-annually
by the terms of the National Fire Code
and NFPA 17, 17A and 96. Fusible
links must be changed annually or more frequently if mandated by
the manufacturer. It is imperative to ensure the cooking appliances'
fuel sources are properly interrupted upon activation of the fire
suppression system. Therefore testing does mean that a shutdown
of the cooking equipment is required. Inspection reports must be
kept by the owner/manager for examination by the insuring agent
and/or the authority having jurisdiction.
Owner/managers should be aware of the ULC
Other Recognized Document C-1254.6, which spells out new standards
for "Restaurant Cooking Area Fire Extinguishing Systems".
Changes to existing hazards (appliances, exhaust ductwork and canopies)
can invoke a necessity to upgrade existing fire suppression systems
to meet this improved standard.
|
 |
| (Sample
Suppression Inspection Report -
14K
) |
Water Wash Systems
As Water Wash Systems are often used in conjuction with, or in
place of, Kitchen Fire Suppression Systems, they too should be inspected
semi-annually to ensure they operate in accordance with the manufacturers
instructions. A malfunctioning pump, or a clogged drain is all too
often found too late, resulting in costly repairs or clean ups.
Pro-active, reasonably priced, regular maintenance and inspections
can keep the automatic systems running smoothly for years to come.
|
 |
|
|
Kitchen Exhaust Cleaning
The fan, exhaust ductwork, canopy and filters in any commercial
kitchen regularly gets coated with grease in the course of normal
usage. Grease build up of this nature can be a serious fire hazard
if it is left unattended. NFPA
96 stipulates that the entire exhaust system should be inspected
on a regular basis. Depending on the type of appliance fuel, foods
cooked and frequency of usage, this can range from monthly to annually.
Should this inspection reveal deposits from grease-laden vapours,
cleaning of the entire system down to bare metal is required. Upon
completion a label, indicating the date, areas found to be inaccessible,
and the name of the contractor, should be applied to the canopy.
Pyrene has the ability to perform both
the cleaning and the fire suppression system inspection simultaneously.
This ensures:
- No accidental discharges of your fire suppression system during
cleaning
- The entire hood, including fire suppression system cable activation
assembly will be cleaned. All too often the cable/conduit assembly
becomes clogged with grease. This buildup could actually prevent
the proper operation of the fire suppression system.
- Less hassle for you and your staff. One service call is sufficient,
meaning less after-hours appointments for you.
|
|
Industrial Fire Suppression Systems
Industrial Fire Suppression Systems, like Kitchen Fire Suppression
Systems, require maintenance and inspections semi-annually under
NFPA 17. As these systems are
not widely applied, our technical staff undergoes stringent training
in order to be able to provide these specialized services.
|
 |
Fire Hydrants
Fire Hydrants are the Fire Departments main source of extinguishing
media. A non-operational hydrant could result in the loss of an
entire structure. The National Fire Code
requires an inspection be performed semi-annually and after each
use. Flushing is required annually. Traditionally, these inspections
are performed in spring and in fall, prior to freeze up. This ensures
there is no accumulation of water in the barrel, which can result
in costly repairs.
|
 |
| (Sample
Fire Hydrant Inspection Report -
68K
) |